Application
BSA1(EH) series AC contactors is mainly used in the electric power circuit of AC 50Hz or 60Hz, rated voltage to 660V, current to 800A for making and breaking circuit, and it can be formed into motor starter with thermal relay or electronic protector for protecting from overload circuit.
Main technical parameter
|
BSA1(EH) |
6 |
9 |
12 |
16 |
25 |
32 |
40 |
50 |
63 |
75 |
|
Ui V |
690 |
|
Ith A |
20 |
26 |
28 |
28 |
45 |
65 |
100 |
125 |
125 |
125 |
|
Ue V |
220 |
|
380 |
|
|
|
Under
Interruption
Period
Operation
System le
(A) |
AC-1 |
20 |
22 |
24 |
28 |
45 |
55 |
70 |
100 |
115 |
125 |
|
AC-3
|
6
6
|
9
9
5.5 |
12
12
7 |
16
16
7 |
25
25
15 |
30
30
17.5 |
40
40
28 |
50
50
38 |
63
63
46 |
75
75
55 |
|
AC-4
|
6
6
|
9
9
5.5 |
12
12
7 |
16
16
7 |
25
25
15 |
30
30
17.5 |
40
40
28 |
50
50
38 |
63
63
46 |
75
75
55 |
|
AC-3 Pe
Kw |
1.5
2.2 |
2.2
4
4 |
3
5.5
5.5 |
4
7.5
5.5 |
6.5
11
11 |
9
15
15 |
11
18.5
22 |
15
22
30 |
18.5
30
37 |
22
37
45 |
|
Non-interrupt
Operation Ie(A) |
20 |
22 |
24 |
28 |
45 |
55 |
70 |
100 |
115 |
125 |
|
BSA1(EH) |
80 |
90 |
100 |
145 |
175 |
210 |
260 |
300 |
370 |
550 |
700 |
800 |
|
Ui V |
690 |
|
Ith A |
145 |
160 |
200 |
230 |
260 |
300 |
400 |
445 |
550 |
800 |
1000 |
1000 |
|
Ue V |
220 |
|
380 |
|
660 |
|
Under
Interruption
Period
Operation
System le
(A) |
AC-1 |
145 |
160 |
200 |
230 |
260 |
300 |
400 |
445 |
550 |
800 |
1000 |
1000 |
|
AC-3 |
80
80
65 |
90
90
70 |
120
120
120 |
145
145
120 |
185
185
170 |
210
210
210 |
260
260
250 |
305
305
280 |
400
400
370 |
550
550
550 |
700
700
700 |
750
750
750 |
|
AC-4 |
80
80
30 |
80
80
35 |
117
117
47 |
125
125
55 |
146
146
66 |
175
175
55 |
250
250
95 |
250
250
95 |
350
350
117 |
450
450
140 |
630
630
185 |
630
630
185 |
|
AC-3 Pe
Kw |
22
40
45 |
22
45
59 |
30
55
110 |
45
75
110 |
55
90
132 |
59
110
160 |
80
140
200 |
90
160
250 |
110
200
355 |
160
280
500 |
220
370
600 |
220
400
650 |
|
Non-interrupt
Operation le(A) |
145 |
160 |
200 |
230 |
260 |
300 |
400 |
445 |
550 |
800 |
1000 |
1000 |
|
Aux
Contacts
Code |
Ith
A |
UI
V |
Ue V |
Ie A |
Contacts type and quantity |
Rated controlling capability |
|
AC |
DC |
AC |
DC |
AC(VA) |
DC(W) |
|
BSA1(EH)F1 |
10 |
690 |
127 |
48 |
0.8 |
0.63 |
NO1 or NC1 |
100 |
30 |
|
220 |
60 |
0.45 |
0.5 |
|
BSA1(EH)F2
BSA1(EH)F3 |
380 |
110 |
0.26 |
0.27 |
NO1
NC1 |
|
660 |
220 |
0.15 |
0.14 |
Installation dimensions

|
Basic pecification |
A max |
B max |
C max |
a |
b |
d |
F |
|
BSA1(EH)-6 |
54 |
58 |
48 |
35?36 |
50 |
4.5 |
|
|
BSA1(EH)-9~16 |
46 |
75 |
82 |
35 |
60?55?50 |
4.5 |
15 |
|
BSA1(EH)-25 |
55 |
92 |
95 |
45 |
80?75?70 |
4.5 |
15 |
|
BSA1(EH)-32 |
55 |
92 |
110 |
45 |
80?75?70 |
4.5 |
15 |
|
BSA1(EH)-40~75 |
71 |
112 |
110 |
60 |
100?90 |
6 |
20 |
|
BSA1(EH)-80~90 |
103 |
132 |
138 |
90 |
100 |
5.5 |
30 |
|
BSA1(EH)-100 |
125 |
158 |
144 |
110 |
120 |
5.5 |
40 |
|
BSA1(EH)-145 |
125 |
174 |
144 |
110 |
120 |
5.5 |
40 |
|
BSA1(EH)-175~210 |
137 |
200 |
170 |
120 |
140 |
6.5 |
15 |
|
BSA1(EH)-260~300 |
177 |
210 |
176 |
160 |
140 |
6.5 |
30 |
|
BSA1(EH)-370~550 |
200 |
273 |
227 |
170 |
200 |
6.5 |
40 |
|
BSA1(EH)-700 |
245 |
296 |
227 |
220 |
200 |
6.5 |
40 |
|
BSA1(EH)-800 |
245 |
346 |
227 |
220 |
200 |
6.5 |
40 |

|
Basic Secification |
A max |
B max |
C max |
a |
b |
d |
F |
|
BSA1(EH)-6 |
54 |
58 |
48 |
35?36 |
50 |
4.5 |
|
|
BSA1(EH)-9~16 |
46 |
75 |
82 |
35 |
60?55?50 |
4.5 |
15 |
|
BSA1(EH)-25 |
55 |
92 |
95 |
45 |
80?75?70 |
4.5 |
15 |
|
BSA1(EH)-40~75 |
92 |
112 |
110 |
60 |
100?90 |
6 |
20 |
|
BSA1(EH)-100 |
165 |
158 |
154 |
120 |
140 |
6.5 |
40 |
|
BSA1(EH)-145 |
165 |
172 |
154 |
120 |
140 |
6.5 |
40 |
|
BSA1(EH)-175 |
201 |
198 |
175 |
160 |
140 |
6.5 |
15 |
|
BSA1(EH)-210 |
201 |
198 |
175 |
160 |
140 |
6.5 |
15 |
|
BSA1(EH)-370 |
270 |
273 |
227 |
220 |
200 |
6.5 |
40 |
|
BSA1(EH)-550 |
270 |
273 |
227 |
220 |
200 |
6.5 |
40 |
|